Mv Surge Capacitor

Product Details
Customization: Available
Type: High Voltage Capacitor
Application: General Purpose, Power, High Voltage
Manufacturer/Factory & Trading Company

360° Virtual Tour

Diamond Member Since 2018

Suppliers with verified business licenses

Audited Supplier

Audited by an independent third-party inspection agency

Number of Employees
76
Year of Establishment
2002-06-24
  • Mv Surge Capacitor
  • Mv Surge Capacitor
  • Mv Surge Capacitor
  • Mv Surge Capacitor
  • Mv Surge Capacitor
  • Mv Surge Capacitor
Find Similar Products
  • Overview
  • Our Advantages
  • FAQ
Overview

Basic Info.

Model NO.
FAM
Packaging Type
Plywood
Capacitance
50-100uf
Structure
Fixed Capacitor
Manufacturing Material
Polypropylene
Electrolyte
Electrolytic
Usage
Tuning, Filter, Compensation
Tuning
Polystyrene Capacitor
Filter
Aluminum Electrolytic Capacitor
Capacitance Tolerance
0%-5%
Transport Package
Plywood
Specification
200-500kvar
Trademark
Sanhe
Origin
China
HS Code
8537209000
Production Capacity
10000PCS\Year

Product Description


Product feature



Technology Specification
  • Introduction
High-voltage shunt capacitor is a simple, economical and reliable reactive power compensation core electrical component, used in 50Hz AC power system, mainly used to improve system power factor, improve grid power quality, reduce voltage drop, reduce power loss, enhance the transmission ability of the system, improve the efficiency of power generation, transmission and power supply. The capacitor uses full film of the surface-roughened polypropylene and PCB-free, safe and environmentally friendly insulating oil as the impregnating agent.
  • Reference standard
IEC 60871-2005, MOD "Shunt capacitors for AC power systems with a nominal voltage above 1000V"
GB/T 11024.1-2010 "Shunt capacitors for AC power systems with a nominal voltage above 1000V"
  • Model Description
The representative meaning of the model of the capacitor is as follows
                  
  1. Impregnation agent: A benzyltoluene
F diaryl ethane
  1. Number of phases: 1 means a single-phase capacitor; 3 means a three-phase capacitor.
  2. Endnote numbers: "W" means outdoor products, "G" means plateau indoor products, "WG" means plateau outdoor products, and no endnote means indoor products.
 
  • Conditions of Use
  1. The installation site should be free from corrosive gas and steam, conductive or explosive dust, and no violent vibration.
  2. The altitude of the installation site is ≤1000m.
  3. Ambient air temperature range: BFM type is -25/ C , BAM type is -40/ C , the letter represents the upper limit of the temperature range, see the table below for details. Users have special requirements can be specified when ordering.
Ambient temperature, °C
code name Highest 24h average
highest
The highest annual average
A 40 30 20
B 45 35 25
C 50 40 30
D. 55 45 35
Note: These temperature values can be found in the meteorological temperature table in the installation area.
Remarks: The capacitor temperature category for this project is -25/D.
  • Technical Parameters and Features
  1. Three-phase rated capacity: 100kvar, 150kvar, 200kvar
  2. Rated voltage: 3.3kV
  3. The polypropylene film adopts double-sided roughened full-film manufacturing technology, which has low loss and good insulation performance. The loss tangent value at 20°C is not more than 0.02 % .
  4. The aluminum foil adopts edge folding technology to improve the stability and service life of the capacitor, and is welded seamlessly by machine, with low impedance, less heat generation, and small deviation, and the range does not exceed ±5% of the rated value. The ratio of the maximum value to the minimum value of the phase capacitance of a three-phase capacitor is not greater than 1.02.
  5. The impregnating agent adopts non-toxic and environmentally friendly insulating oil, which has small partial discharge and slow aging.
  6. The shell is made of high-quality steel plate bent and welded, using advanced stamping technology, smooth and beautiful, with high mechanical strength.
  7. Each series and parallel section of the capacitor core is equipped with a discharge resistor, and the residual voltage can drop from √2Un to below 75V within 10 minutes. In addition to power-off discharge, it can also eliminate the overvoltage caused by the action of the internal fuse.
  8. Overload capacity
1) Allowable voltage levels during operation:
type Voltage Un maximum duration illustrate
power frequency 1.00 continuous Highest average value over any period of capacitor operation
power frequency 1.10 8h in every 24h Adjustment fluctuations in system voltage
power frequency 1.15 30min every 24h Adjustment fluctuations in system voltage
power frequency 1.20 5min Voltage boost at light load
power frequency 1.30 1min
Note: Un is the rated voltage of the capacitor
  1. The long-term steady-state overcurrent is 1.3 times the rated current, and for capacitors with the maximum positive deviation of the capacitance value, this overcurrent can reach 1.37 times the rated current.









 
  • Capacitor model and drawing
  1. Conventional model selection
  2. Conventional Model Outline Drawing
Model Specifications Size parameters Capacitance electric current
W h1 h2 h
BAM 3.3-10 0-3W _ _ _ _ 150 150 223 250 29.2μf 17.5A
BAM 3.3-15 0-3W _ _ _ _ 150 150 223 300 43.9μf 26.2A
BAM 3.3-20 0-3W _ _ _ _ 150 150 223 375 58.5μf 35.0A
 
  • Shipping and Handling
  1. When transporting and hoisting capacitors, it is strictly forbidden to lift, pull, or push the outlet bushing, so as not to cause the bushing to loosen and cause oil leakage.
  2. When the capacitor is transported, it should generally be carried out with packaging, especially when it is transported to a distant place. There should be a soft pad in the packaging box, and the outlet sleeve should be in an upright state without any additional mechanical stress.
  3. The transportation method of capacitors to the installation site is mainly road or rail transportation.
  4. During the transportation of capacitors, attention should be paid to the weather, and measures should be taken to prevent rain and snow.
  5. Capacitors should be placed vertically during transportation and moving to prevent collisions and falls.
  6. It is strictly forbidden to carry and move the capacitor with the porcelain sleeve as the stress point.
  7. The loading and unloading of the product should strictly follow the relevant national loading and unloading regulations. During the whole loading and unloading process, it should be handled with care and balanced to ensure the safety of people and equipment.
  • Storage
  1. Products that need to be stored should be stored in a dry, rainproof and dust-free house or shed after acceptance, to avoid the radiation of high-temperature heat sources and the erosion of steam and other corrosive gases. The ambient air temperature should be -40 ° C ~ +40°C range.
  2. During the storage period, capacitors with packing boxes should be placed according to the requirements on the packing boxes. Unpackaged capacitors should be placed upright with the casing facing upwards. Capacitors are not allowed to be stacked, and warehouses with active chemicals and corrosive materials should not be stored at the same time.
  3. Non-outdoor products should not be placed outdoors. If they need to be placed for a short time, they should be well packaged and padded with wooden squares, with a height of not less than 100mm.
  • Install
  1. Capacitor installation method: vertical installation.
  2. When the capacitor bank is installed, the distance between each capacitor is generally not less than 60mm to ensure heat dissipation.
  3. Before the complete installation of capacitors, the capacitors should be distributed evenly according to the capacitance value, so that the error of capacitance value between phases after installation and between each series section of each phase is the smallest, so as to ensure the stable operation of the whole set of devices.
  4. During the installation of the capacitor, first use a wrench to fix the boss on the terminal block, and then use another wrench to loosen the nut on the guide rod. Oil leakage is caused by excessive force at the junction of the terminal.
  5. The lead-out wire of the capacitor bushing shall not directly use the hard conductive bus bar, but shall use the tinned annealed copper stranded wire.
  6. The arrangement of the capacitors on the mounting frame should make the nameplate outward, which is convenient for the staff to check.
  7. Install the external fuses according to the fuse installation instructions.
  • inspection and testing
  1. When the user receives the capacitor, the product should be inspected for acceptance.
  2. Appearance inspection: Check the paint condition of the capacitor, whether the casing and outlet bushing are damaged, and whether there is oil leakage, and pay attention to the correctness of the data on the nameplate.
  3. If necessary, conduct a voltage test on the capacitor. The voltage test includes the AC voltage test between the poles and the AC voltage test on the pole shell.
1) Inter-electrode AC voltage test: The test voltage value is 75% or lower of the factory test voltage (2.15 times the rated voltage) and lasts for 2s.
2) Pole-to-shell AC voltage test: the test voltage value is 75% or lower of the factory test voltage, and lasts for 10s.
  1. Capacitance and loss test: The measured capacitance value should be consistent with the value indicated on the nameplate (considering the measurement error).
  2. The built-in discharge device (if any) can be tested by measuring resistance.
  3. After the capacitor is put into operation, it should be checked regularly according to the duty inspection system whether the capacitor is leaking oil, whether the temperature rise is too high, whether the voltage and current exceed the allowable value, and the capacitor should be taken out of operation when abnormal conditions are found.
  4. The ambient temperature where the capacitor is installed should be controlled below the specified maximum temperature. If it is exceeded, forced cooling should be used to reduce the temperature. If forced cooling still does not work, the capacitor should be taken out of operation.
  5. Regularly clean the capacitor outlet bushing, clean the installation site, and check the reliability of the conductive connection and the blown display of the external fuse.
  6. Before the cause of the protection action is found out, the capacitor should not be put into operation again; for the capacitor whose protection has been activated, it should be confirmed that it is in good condition before it can be put into operation again.
   
   
   
   
   
   
   
System voltage≤1000V,technology parameter of capacitor
Rated capability: 25kvar-500kvar
Rated frequency: 50Hz or 60Hz
Average dielectric loss power: ≤0.2W/kvar
Work temperature: -40/D(+55C)
Capacitor structure: Single-phase or three-phase
Shell material: Single-phase or three-phase
Executive standard: GB/T 11024
Special requirement can be customized!

Mv Surge Capacitor

 
Founded in 2002, Sanhe Power Tech is a national high-tech enterprise that specializes in power quality products, R&D of technology and solutions, production,service etc. It becomes industry-leading company.
The company has got multiple technologies including.
28 invention patents,
24 software copyrights,
22 national standards and 15 industry standards drafting.
Sanhe Power Tech is a member of international committees such as
the International Electrotechnical Commission (IEC)
the Institute of Electrical and Electronics Engineers (IEEE) etc.
The software development system has passed the CMMI evaluation of the American SEI.
There are three main business covering:
A full range of power quality testing and governance products and complete solutions.
Distributed new energy system products and advanced solutions.
Primary and secondary engineering based on "dual carbon" and energy management with standardized and professional engineering services.
Our Advantages

Simulation of GRID Reactive Load Flow
Analysis of L-C Circuit Amplitude-frequency Characteristic
Integration & Relay Coordination Reaction
Characteristic Curve of Permanent Magnet Breaker
Sampling & Filtering of Electronic Circuit
IGBT Driving & Protection
PWM Technology
Technology about Semiconductor Forced Commutation
Thermal Simulation & Heat Exchange Design
Feed-forward Second-order Complex Vector Algorithm
3D & Data Simulation
Instrumented IOT Communication
VP Scheduling & Dispatcher
Digital Twins of Micro-Grid & Islanding-Grid

 

FAQ

What kind of payment terms can we accept?

Payment in advance,Installment payments,Letter of credit(L/C).
 

What is the lead time of products?

According to different products, the lead time is different.
For standard products like APF,SVG, the lead time is one week.
For customized capacitor bank etc,  the lead time is 25 to 45 days.
 

How to find the product model if you are some demand?

If you need our technical guide,please advise your problem details as much as you can,we can give more reasonable solution.
You may provide following drawings or report
Single line drawing
Panel primary scheme drawing
Power quality test report(mainly about harmonics)
 

How to find the product model if you have details electrical drawings?

Please advise Load name plate, load working condition, existing power factor, target power factor, harmonic times etc Or Rated voltage,compensation capacity, harmonic times(reactor detuning factor), other components etc.
 

How to find the product model if you can not provide enough information?

We can supply your products according to your technical requirement.
We can go to your project site and give a professional test report after test.
 

Why do we choose Sanhe power quality solution?


Sanhe has specialized in over 20 years experience in power quality products and solution. We have met most of power quality problems and gave the solutions.

What kind of technical service does Sanhe provide?

• Project-site power quality test ( or test report from customer)
• Improvement solution and budget
• Product solution and price
• Products supply
• Product commissioning

What kinds of standards does Sanhe product conform to?

Except China standards, Sanhe products also conform to IEC standards including
IEC61921 :2003 IEC61000-4-5:2005
IEC60529:2001 IEC60931-1: 1996
IEC60439-1 :2005 IEC60664-1 2007
IEC60831-1: 1996 IEC61000-4-3/2/4/5/18 IEC61000-2-4
IEC60255 IEC62208 2011…
IEC255-22-1

What is the compensation effect after using Sanhe products?
• Harmonic filtering meets standard
• Power factor is over 0.95,electrical bill saving,low reactive power penalty killing
• Reducing the loss of transformer and line
improve the distribution ability,
prolong the lifespan of electrical equipment

How long is the product guarantee time?

Usually,the guarantee time is one year. However,we can accept over 5 years too. Please contact our sales to get details information.

How to become the distributor or agent of Sanhe brand products?

Sanhe is looking for overseas distributor and agent. If you are interested in it, please feel free to contact us.
 

 

 

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now
Contact Supplier