| Customization: | Available |
|---|---|
| Electricity Type: | Vacuum |
| Number of Pole: | 3 |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
| Technical data | SEK-7P-200/400/630 | SEK-10P-200/400/630 | |
| Rated voltage | Ur(kV) | 7.2 | 12 |
| Rated current | Ie(A) | 200/400/630 | 200/400/630 |
| Rated frequency | fr(Hz) | 50-60 | 50-60 |
| Rated short-time withstand current | Ik(kA) | 4 | 6.3 |
| Rated peak withstand current | Ip(kA) | 10 | 16 |
| Rated short circuit breaking current | Io(kA) | 4 | 5 |
| Rated short-circuit making current | Ic(kA) | 10 | 12.5 |
| capacitive switch current | Itc(A) | 230 | 230 |
| Operating frequency | (Times/hour) | 900 | 900 |
| Mechanical life | (Times) | 30×104 | 30×104 |
| Electrical life | (Times) | AC-3:25×104 | AC-3:25×104 |
| (Times) | AC-4:10×104 | AC-4:10×104 | |
| Rated lightning impulse withstand voltage | Up(kV) | 60 | 75 |
| Rated power frequency withstand voltage (1min) | Ud(kV) | 32 | 42 |
| Three-phase closing synchronization | (ms) | ≤2.0 | ≤2.0 |
| Contact bounce time | (ms) | ≤5.0 | ≤5.0 |
| Conductive loop resistance of each phase (20ºC) | (μΩ) | ≤180 | ≤180 |
| Control loop | |||
| Control module- rated operating voltage | Ur(V) | 110V/220V(AC,DC) | |
| Rated operating voltage range | (V) | 0.85Ur~1.1Ur | |
| Latching mode | Permanent magnet | ||
| Operating power | DC110V,3A | ||
| DC220V,1.5A | |||
| AC220V,1A | |||
| Closing time | (ms) | ≤50 | |
| Inherent opening time | (ms) | ≤20 | |
| 1min power frequency withstand voltage | (kV) | 2 | |
| Auxiliary contacts-quantity | 5 open 5 close | ||
| Conventional heating current | (A) | 6 | |
| Mechanical life | (Times) | 5×106 | |
| Electrical life | (Times) | 2×106 | |
| Rated working current | DC/AC110V,0.4A | ||
| DC/AC220V,0.2A | |||