Voltage(kV) |
Rated current |
Short time withstand current(3s) |
Switch Type |
Insulation type |
Structure |
Remark |
12/24 |
630A |
20kA |
DES(LBS) |
SF6 |
Max.6 loops |
standard |
Rated Voltage | kV | 12 | 24 |
Rated Frequency | Hz | 50/60 | |
Power Frequency Withstand Voltage (1min)(Phase to Phase, Phase to Earth) | kV | 42 | 50 |
Power Frequency Withstand Voltage (1min)(Isolation Gap) | kV | 48 | 60 |
Lightning Impulse Withstand Voltage(Phase to Phase, Phase to Earth) | kV | 75 | 125 |
Lightning Impulse Withstand Voltage(Isolation Gap) | kV | 85/95(optional) | 145 |
Rated Current | A | 630 | 630 |
Rated Active Load Breaking Current | A | 630 | 630 |
Closed Loop Breaking Current | A | 630 | 630 |
Rated Breaking Current for Cable Charging | A | 10 | 10 |
Rated Earthing Fault Breaking Current | A | 31.5 | 31.5 |
Rated Short Circuit Making Current(Peak) | kA | 50 | 50 |
Short Time Withstand Current (4s) | kA | 20 | 20 |
Rated Peak Withstand Current (Peak) | kA | 50 | 50 |
Mechanical Endurance | Operating Cycles | 5000 | 5000 |
Rated SF6 Filling Pressure (Relative) | MPa | 0.03 | 0.035 |
Protection Degree | IP67 for Gas Tank, IP4X for Enclosure outdoor enclosure IP54(optional) |
||
Overall Dimensions(Width*Height*Depth)mm | 340*1450*780 |