Customization: | Available |
---|---|
Certification: | ISO9001, CCC, Type Test |
Protection: | IP44 |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
AC port (grid-connected) | |||
Rated power KW | 50 | 100 | 150 |
Maximum power KVA | 55 | 110 | 165 |
Rated current A | 72 | 144 | 216 |
Maximum current A | 79 | 158 | 240 |
Rated voltage | 400Vac (-20% to 15%), 3W+N+PE | ||
Rated frequency | 50/60hz ±5 | ||
Current Distortion (THDI) | <3% of rated power | ||
Power factor adjustment range | ±1 | ||
DC/AC circuit topology | Three-level DC/AC | ||
AC side parameters (grid-connected) | |||
Rated power KW | 50 | 100 | 150 |
Rated voltage | 400Vac | ||
Output voltage distortion | <2% linear load | ||
With unbalanced load capacity | 100% | ||
overload capacity | 110% - normal operation, 120% - 1 minute | ||
PV side | |||
Maximum PV input voltage | 1000V | ||
Maximum input power KW | 100 | 200 | 200 |
MPPT voltage range | 200-850V | ||
MPPT channels | 4 | 8 | 8 |
DC/DC circuit topology | Three-level DC/DC | ||
battery side | |||
battery voltage range | 400-900Vdc | ||
Full load voltage range | 400-850V | ||
Maximum quantity of battery input channels | 5 way | ||
General parameter | |||
maximum efficiency | 97.60% | 97.90% | 97.90% |
Dimension mm | 1000x950x2000 | ||
Weight KG | 720 | 750 | 850 |
isolation method | non-isolated | non-isolated | non-isolated |
Protection class | IP54 | ||
Operating temperature | - 25 to 60 °C | ||
cooling method | smart air cooling | ||
noise | <70dB | ||
Altitude | 3000M (over 3000M derating) | ||
Communication Interface | RS485/CAN 2.0/Ethernet/Dry contact |