Customization: | Available |
---|---|
Certification: | ISO9001, CCC, Type Test |
Protection: | IP44 |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Model | Symonet-100 | Symonet-250 | Symonet-500 | Symonet-250T | Symonet-500T |
DC side parameters | |||||
Operating voltage range | 550-900V | 550-900V | 550-900V | 550-900V | 550-900V |
Full load voltage range | 550-900V | 550-900V | 550-900V | 550-900V | 550-900V |
Maximum DC current | 100A*2 | 100A*5 | 100A*10 | 110A*5 | 110A*10 |
Number of input channels | 1/2 | 1/5 | 1/10 | 1/5 | 1/10 |
Adapter battery | Lithium battery/lead acid/photovoltaic module | ||||
charging method | According to BMS instruction, three-stage, MPPT | ||||
Operating mode | Constant voltage, constant current, constant power, MPPT, AC voltage source, DC voltage source, VSG | ||||
AC side parameters (grid-connected) | |||||
Maximum AC power | 110kVA | 275kVA | 550kVA | 722kVA | 550kVA |
Rated AC power | 100kW | 250kW | 500kW | 250kW | 500kW |
Rated AC current | 144A | 361A | 722A | 361A | 722A |
Rated AC voltage | 400Vac, 3W+N+PE/3W+PE | ||||
AC voltage range | 400Vac, ±15% | ||||
Rated frequency | 50/60hz ±5 | ||||
Current Distortion | <3% (rated power) | ||||
Power factor adjustment range | ±1 | ||||
Protective function | |||||
DC input protection | Load switches and fuses | ||||
AC input protection | Circuit Breakers and Fuses | ||||
Over voltage protection | DC Type II /AC Type II | ||||
Overcurrent Protection | YES | ||||
Residual current detection | YES | ||||
Anti-islanding protection | YES | ||||
Conventional Parameter | |||||
maximum efficiency | 98.20% | 98.20% | 98.40% | 97.40% | 97.40% |
KVA | 600x750x2000 | 600x750x2000 | 1200x750x2000 | 1200x900x2000 | 1600x900x2000 |
Weight KG | 240 | 350 | 800 | 1200 | 1650 |
isolation method | non-isolated | non-isolated | non-isolated | Power frequency isolation | Power frequency isolation |
Protection class | IP21 | ||||
Operating temperature | - 25 to 60 °C | ||||
Relative humidity | 0-95%°C | ||||
cooling method | forced air cooling | ||||
noise | <70dB | ||||
Altitude | <5000M | ||||
Communication Interface | RS485/CAN 2.0/Ethernet | ||||
standard | EN 61000-6-1 / EN 61000-6-2 / EN 61000-6-3 IEC 61000, IEC 62477-1:2012, IEC 61727, IEC 62116, GB /T34120, GB /T34133 |