Customization: | Available |
---|---|
Type: | Harmonic Filter |
Capacity: | 35A,50A,75A,100A,150A |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Altitude | <1500m, 2000m-4000m derating |
Relative humidity | 5%RH-95%RH, non-condensing |
Operating temperature | -10 oC ~50 oC (> 40 oC, derating) |
Operating environment | In-door, free from moisture, dust, corrodent or flammable gases, oil mist, vapor, water leakage or salt water. |
Storage/Shipment temperature | -40 oC ~70 oC |
Vibration | Less than 5.9m/s2 (0.6g) |
Item | Description | |
Function | Main | Harmonics Compensation |
protection | Over voltage protection, under voltage protection, short circuit protection, reverse protection of inverter bridge, over compensation protection | |
Harmonic Degree | 2 ~ 51 times can be adjusted to any number of times | |
Application | Hotel,Car park, Car charger station,Car 4S store,IDC, hospital,Railway,water treatment and other non-liner load. | |
Electrical Electrical |
Rated voltage | 480Vac |
Wiring | 3P4W/3P3W | |
Frequency | 50/60±3Hz | |
Capacity | 20~150A | |
Parallel units | Unlimited(customized acceptable) | |
Filtering capability | THDi(Current distortion rate)<5% | |
switching frequency | 20kHz | |
Response time | Fast response time <50μs Total response time<5ms |
|
Dry Contact | EPO,DI,DO | |
CT ratio | 150:5~6000:5 | |
Enclosure | Protection degree | IP20,The rest of the IP level can be customized |
Colour | 7035 grey (customized acceptable) | |
Size | According to type | |
Cooling | Fan cooling,noise:<56dB | |
Communication | Remote | RS485/Ethernet |
Local | RS485 | |
Protocol | CAN/MODBUS TCP |
APF20A 30A | APF50A 75A 100A | APF 125 A 150A | |
size (w*d*h mm) |
Rack type:442*485*90 Wall mounted:442*90*485 |
Drawer type:500*590*150 Wall mounted:505*175*64 Vertical type:170*525*590 |
Drawer type:500*590*170 Wall mounted:505*195*640 Vertical type:170*525*590 |
Net Weight | 20KG | 35KG | 45KG |
Transformer(KVA) | APFM (3P3W) | APFM (3P4W) |
500 | 100A | 150A |
800 | 200A | 250A |
1000 | 200A | 300A |
1250 | 300A | 400A |
1600 | 400A | 500A |
Remark | 1.Under bad condition application, industrial cabinet type APF is recommended. 2.While harmonic current or reactive power is too big, please measure data on project site at first. |