Customization: | Available |
---|---|
Altitude: | 4000meter |
Transport Package: | Plywood Carton |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Basic parameters | ||
Type of load | Three-phase squirrel cage asynchronous and synchronous motors | |
AC voltage | 3000---10000VAC | |
Service frequency | 50HZ/60HZ±2HZ | |
Phase sequence | allowed to work with any phase sequence (through setting parameter) | |
Composition of major loop | (12SCRS,18SCRS,30SCRS depend on model) | |
Bypass contactor | Contactor with direct starting capacity | |
Control power | AC220V±15% | |
Transient voltage overload | dv/dt snubber network | |
Start frequency | 1-6 time per hour | |
Ambient condition | Ambient temperature:-20°C -+50°C | |
Relative humidity:5%----95% no condensation | ||
Altitude less than 1500m(derating when altitude is more than 1500m) | ||
Protective functions | ||
Open-phase protection | Cut off any phase of primary power supply in the courage of starting or operation | |
Over-current protection in operation | Operational Over-current protection setting:20~500%le | |
Unbalanced phase current protection | Unbalanced phase current protection:0~100% | |
Overload protection | Overload protection grade:10A,10,15,20,25,30 | |
Under load protection | Under load protection grade:0~99% Action time of under load protection:0~250S | |
start timeout | Start timeout limit:0~120S | |
Over-voltage protection | When voltage of primary power supply is 120% higher than rated value,over-voltage protection is enabled. | |
Under-voltage protection | When voltage of primary power supply is 70% higher than rated value,over-voltage protection is enabled. | |
Phase protection | Allow to work with any phase sequence(through setting parameter) | |
Ground protection | Protection available when grounding current is higher than set value | |
Description of communication | ||
Protocol | Modbus RTU | |
Communication interface | RS485 | |
Network connection | Each can communicate with 32 SH-SPHMV equipment in network | |
Function | Operation state and programming can be observed through communication interface | |
Operating interface | ||
LCD display | LCD display/touch screen display | |
Language | Chinese an English | |
Keyboard | 6 touch membrane keyboard | |
Meter display | ||
Voltage primary power supply | Display voltage of three-phase primary power supply | |
Three-phase current | Display current of three-phase major loop | |
Date record | ||
Fault history | Record recent 15 faults information | |
History of number of starts | Record number of starts of this soft starter |
Medium voltage reactor soft starter | Medium voltage solid soft starter | ||
Principle | The reactance is connected in series in the stator circuit of the motor, and the starting multiple control of the current is realized by sharing the voltage at the motor end. |
Parallel thyristors are connected in series in the stator circuit of the motor, and the conduction angle of the thyristor is adjusted through the closed-loop control system to gradually increase the motor terminal voltage and realize the starting of the motor. | |
voltage execution | reactor | thyristor (SCR) | |
usage application | 380V-10KV,100-3000KW | 380V-10KV,100-10000KW, specially suitable for big capacity motor | |
Starting process controllability | not controllable | Closed loop control to realize constant current starting | |
repeatability | Continuous starting, good repeatability | Continuous starting, good repeatability and controlled current | |
lifespan | above 15 years | above 20 years | |
response time | slow(class second) | fast (class: millisecond) | |
protection | Over time protection | Overcurrent, quick break, timeout, overvoltage, undervoltage, current imbalance, overload, underload, thyristor short circuit protection | |
measuring function | NO | current, voltage | |
soft-starting | NO | YES |